ABB ACS580 4210: IGBT overtemperature
What it means Estimated drive IGBT temperature is excessive.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Cooling problem
- Overload
Checks, in order
- Check ambient conditions
- Check air flow and fan operation
- Check heatsink fins for dust
- Check motor power against drive power
Source
Source (reworded, not copied): ABB, ACS580 Standard Control Program Firmware Manual, 3AXD50000016097 Rev J (2025-10-01), Fault tracing, PDF page 554. Official manual (PDF). Fault numbers and names can differ between firmware versions.