Siemens SINAMICS G120 F07801: Drive: Motor overcurrent
What it means The permissible motor limit current was exceeded.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Current limit set too low
- Up ramp too short or load too high
- Short or ground fault in the motor cable
- Motor data not matching
Checks, in order
- Check the current limit (p0640)
- Lengthen the up ramp (p1120) or reduce load
- Check motor and cables for short and ground fault
- Check star-delta and nameplate data
Source
Source (reworded, not copied): Siemens, SINAMICS G120 Control Units CU240B-2/CU240E-2 List Manual, 02/2023, A5E33839529, section 4.2 List of faults and alarms, PDF page 881. Official manual (PDF). Fault numbers and names can differ between firmware versions.