Siemens SINAMICS G120 F07901: Drive: Motor overspeed
What it means Motor speed went past the maximum allowed (speed limit p1082 plus hysteresis p2162).
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Overhauling load pushing the motor
- Speed limit or hysteresis set too tight
Checks, in order
- Check r1084 or r1087 and correct p1082 and p2162 if needed
- Consider speed-limit precontrol (p1401.7 = 1)
Source
Source (reworded, not copied): Siemens, SINAMICS G120 Control Units CU240B-2/CU240E-2 List Manual, 02/2023, A5E33839529, section 4.2 List of faults and alarms, PDF page 885. Official manual (PDF). Fault numbers and names can differ between firmware versions.