Siemens SINAMICS G120 F30001: Power unit: Overcurrent
Cites the manual · line-by-line check pending
What it means The power unit saw too much current.
Likely causes
- Short or ground fault on output
- Accel too fast
- Wrong motor data
Checks, in order
- Megger motor and cable
- Check ramp-up
- Recheck motor data/commissioning
Source
Source (reworded, not copied): Siemens, SINAMICS G120 Control Units CU240B-2/CU240E-2 List Manual, 02/2023, A5E33839529, section 4.2 List of faults and alarms. Official manual (PDF). Fault numbers and names can differ between firmware versions.