Allen-Bradley PowerFlex 525 F005: OverVoltage
Cites the manual · line-by-line check pending
What it means DC bus voltage went too high, usually from energy coming back from the motor.
Likely causes
- Decel time too short
- Overhauling load
- High line voltage
- No braking resistor
Checks, in order
- Lengthen decel
- Check line voltage
- Consider bus regulation or a dynamic brake
Old Hand tip
Fast-stopping a heavy fan is the classic cause.
Source
Source (reworded, not copied): Rockwell Automation, PowerFlex 520-Series AC Drives User Manual, publication 520-UM001O-EN-E (September 2025), Chapter 4 Troubleshooting. Official manual (PDF). Fault numbers and names can differ between firmware versions.