Allen-Bradley PowerFlex 525 F015: Load Loss
What it means Output torque current stayed below the Load Loss Level (A490) for longer than the Load Loss Time (A491), as if the load disappeared.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Broken belt or coupling
- Dry pump
- Level or time set too sensitive
Checks, in order
- Verify connections between motor and load
- Check the process
- Verify the A490 and A491 settings
Source
Source (reworded, not copied): Rockwell Automation, PowerFlex 520-Series AC Drives User Manual, publication 520-UM001O-EN-E (September 2025), Chapter 4 Troubleshooting, PDF page 161. Official manual (PDF). Fault numbers and names can differ between firmware versions.