Allen-Bradley PowerFlex 525 F081: DSI Comm Loss
What it means Communication between the drive and its Modbus or DSI master device was interrupted.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Loose or damaged comm cable
- Master device stopped or faulty
- Electrical noise
Checks, in order
- Check comm cabling and the Modbus or DSI settings and status
- Review C125 Comm Loss Action
- Grounding terminals C1 and C2 may improve noise immunity
Source
Source (reworded, not copied): Rockwell Automation, PowerFlex 520-Series AC Drives User Manual, publication 520-UM001O-EN-E (September 2025), Chapter 4 Troubleshooting, PDF page 162. Official manual (PDF). Fault numbers and names can differ between firmware versions.